Главная >>
Каталог >>
Преобразователи напряжения >>
Инверторы серии DCI 48V-600VA
 |
DCI 48V-600VA |
INPUT |
|
Voltage: |
40 -
80 Vdc |
Ripple
current: |
< 2mV Pspho |
Protection: |
Internal circuit
breaker |
Fuse
recommendation: |
20 A |
OUTPUT |
|
Nominal
voltage: |
230 Vac |
Load
effect: |
0 - 8 V from 0
to 100 % load change |
Nominal
frequency: |
50 Hz (chrystal
quartz) |
Nominal
current: |
2,6 Arms |
Nominal
power: |
600 VA at cos
phi = 0,8 ind to 0,9 cap |
Overload
capacity: |
1200 VA for 5
seconds |
Crest
factor: |
2,8 for real
power of 500 W |
Distortion
rate: |
< 1 % with
linear load |
Efficiency: |
> 88 % with a
nominal load, cos phi = 1 |
Response
time: |
200uS for 0 to
100 % and 100 to 0 % load changes |
Protection: |
Internal
electronic protection and a circuit breaker
|
EMC |
|
Conducted
noise: |
VDE 0871 B, EN
55022 |
Radiated
emission: |
EN 55022 |
Immunity: |
IEC 801 |
CONSTRUCTION |
|
Height: |
132 mm |
Width: |
19" |
Depth: |
350 mm |
Weight: |
11 kg |
Protection
class: |
IP20 |
SAFETY |
|
Safety
norm: |
EN 60 950 |
Dielectric
strength: |
4kVdc between
input and output |
|
4kVdc between
output and ground версия для печати |
|
2kVdc between
input and ground |
ENVIRONMENT |
|
Ambient
temperature: |
+0 … +45 C |
Audible
noise: |
< 40 dB(A) |
Parallelling: |
16 modules max. |
MONITORING |
|
Display: |
2 x 16 chrs LCD
for status and measurements display |
Remote
alarms: |
Potential free
change over contacts |
| OPTIONS |
|
|
Integrated
static by-pass switch for non paralleled applications . |
|
|
|
|