Главная >>
Каталог >>
Преобразователи напряжения >>
Инверторы серии DCI 48V-3000VA
 |
DCI 48V-3000VA |
INPUT |
|
Voltage: |
40 - 80 Vdc
|
Ripple current:
|
< 2mV Pspho |
Protection: |
Internal circuit breaker
|
Fuse recommendation:
|
80 A |
OUTPUT |
|
Nominal voltage:
|
230 Vac |
Load effect:
|
0 - 8 V from 0 to 100 % load
change
|
Nominal frequency:
|
50 Hz (chrystal quartz)
|
Nominal current:
|
13 Arms |
Nominal power:
|
3000 VA at cos phi = 0,8 ind to 0,9
cap<
/p > |
Overload capacity:
|
5000 VA for 5 seconds
|
Crest factor:
|
2,8 for real power of 2500 W
|
Distortion rate:
|
< 1 % with linear load
|
Efficiency: |
> 89 % with a nominal load, cos phi =
1<
/p > |
Response time:
|
200uS for 0 to 100 % and 100 to 0 % load
changes
|
Protection: |
Internal electronic protection and a
circuit breaker
|
EMC |
|
Conducted noise:
|
VDE 0871 B, EN 55022
|
Radiated emission:
|
EN 55022 |
Immunity: |
IEC 801 |
CONSTRUCTION |
|
Height: |
222 mm |
Width: |
19" |
Depth: |
350 mm |
Weight: |
18 kg |
Protection class:
|
IP20 |
SAFETY |
|
Safety norm:
|
EN 60 950 |
Dielectric strength:
|
4kVdc between input and output
|
|
4kVdc between output and
ground
|
|
2kVdc between input and ground
|
ENVIRONMENT |
|
Ambient temperature:
|
+0 … +45 C |
Audible noise:
|
< 40 dB(A) |
Parallelling: |
16 modules max. |
MONITORING |
|
Display: |
2 x 16 chrs LCD for status and
measurements display
|
Remote alarms:
|
Potential free change over
contacts
|
| OPTIONS |
|
|
Integrated static by-pass switch for non
paralleled applications .
|
|
|
|
|